SCORE 86 Reroofing Current use: Power plant | Permit id: #200510075132 | |||||
SCORE 100 A new nfs2-30 panel with 1 remote graphic annunicator. The system will include smokes 6 beam detectors 1 pull station 6 dual monitor modules 6 monitor modules 6 pull station for existing deluxe system & 1 weatherproof hornstrobe. Current use: Warehouse no fr | Permit id: #200711158213 | |||||
SCORE 100 Add new wet sprinkler system 15 heads in oil holding over flow room & add new 39 nozzle water spram deluge system on first floor transformer. Current use: Power plant | Permit id: #200711198527 | |||||
SCORE 99 Performing a voluntary seismic strengthening of the electric substation including strengthening exterior connections shear connection constructing new shearwall & horizontal bracing & strengthening low roof diaphragm. See attached project description. Current use: Power plant | Permit id: #200703136168 | |||||
SCORE 56 Reroofing Current use: Power plant | Permit id: #200707267823 | |||||
SCORE 100 Replace existing water spray system at transformer bank 4 with new water spray system (deluge) Current use: Power plant | Permit id: #200812118309 | |||||
SCORE 100 Replace nozzles on (e) water spray system protecting transformer bank 5 reference pa# 2007-1119-8527 Current use: Power plant | Permit id: #200812118312 | |||||
SCORE 100 Reinstall 6 heat detectors in transformer bay #4 for activation of the deluge sprinkler system on ground floor. Current use: Power plant | Permit id: #200812178673 | |||||
SCORE 100 Reinstall heat detectors in transformer bank #5 for activation of the deluge sprinkler system. The system shall include 6 heat detectors around transformer bank #5 Current use: Power plant | Permit id: #200806104011 | |||||
Installing partition wall between transformers Date: November 4, 2009 Value: $52,000 Current use: Power plant | Permit id: #200911040566 | |||||
SCORE 95 Installing partition wall between transformers Current use: Power plant | Permit id: #200911040566 | |||||
SCORE 100 Pg&e sub-station. To supply and install 6 heat detectors in transformer bank # 1 for activation of the existing deluge sprinkler system Current use: Power plant | Permit id: #201003118001 | |||||
SCORE 100 Replace (e) water spray system at transformer bank #1 with new water spray system for the new transformer (e) deluge system Current use: Power plant | Permit id: #201003118007 | |||||
SCORE 100 To obtain final inspection for work approved under pa 200711158213; all work has been completed Current use: Warehouse no fr | Permit id: #201006104246 | |||||
SCORE 100 To obtain final inspectionfor work approved under pa#200711158213 all work has been completed. Current use: Warehouse no fr | Permit id: #201209189982 | |||||
Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Date: November 22, 2013 Value: $185,200 Current use: Food/beverage h | Permit id: #201311222633 | |||||
SCORE 95 Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair preserve original transom window. Current use: Food/beverage h | Permit id: #201311222633 | |||||
SCORE 93 Fire alarm system expansion and replace the graphic annunciator. Remove and replace the sprinkler manifold down the basement. Also install deluge system in bank 2 area to protect the new transformer. Current use: Warehouse no fr | Permit id: #201307081325 | |||||
SCORE 95 Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16. 5 ft high of pre-concrete. Maher n a. Must maintain (e) fire suppression coverage. Current use: Power plant | Permit id: #201407231921 | |||||
SCORE 100 Install kitchen fire suppression system for hood and duct. Type: range guard ul 3 4 gallon. Current use: Food/beverage h | Permit id: #201407302509 | |||||
SCORE 93 Replace (e) deluge & heat detection system to accommodate new transformer. Maher: compliance with ordinance no# 155-13 not required Date: September 5, 2014 Contractor: Wes Mcclain Current use: Power plant | Permit id: #201409055569 | |||||
SCORE 95 Replace the exiting graphic annunciator with new touch screen graphic annunciator. Install new dual monitor modules and releasing control modules to monitor the new water flow and tamper switches. Install nine (9) duct smoke sensor to the existing fire alarm system to monitor the fan units in the basement. Install six (6) high heat sensors in the transformer 2 bay. Add one acps 6 power supply and 7 horn strobes to the fire alarm system Date: July 11, 2013 Contractor: Sierra Electric Co Permit type: Electrical permit | Permit status: Issued | Permit id: Ew20130711041 | |||||
SCORE 95 Life safety for permit #ew20130711041 Date: July 31, 2013 Contractor: Sierra Electric Co Permit type: Electrical permit | Permit status: Complete | Permit id: Ew20130729801 | |||||
Installing partition wall between transformers Value: $52,000 Permit type: Otc alterations permit | Permit status: Expired | Completion date: November 4, 2009 | Expiration date: December 16, 2010 | Current use: Power plant | Permit id: 200911040566 | |||||
SCORE 95 Install 8 heat detections Date: February 17, 2015 Contractor: Sierra Electric Co Permit type: Electrical permit | Permit status: Complete | Permit id: Ew20150213501 | |||||
SCORE 95 Life safety for permit #ew20130711041 2 hour test Date: September 8, 2015 Contractor: Sierra Electric Co Permit type: Electrical permit | Permit status: Complete | Permit id: Ew20150807781 | |||||
As built replace (e) deluge and heat detection system to accomodate new transformer reference 201409055569; maher n/a Value: $1 Permit type: Otc alterations permit | Permit status: Issued | Completion date: February 26, 2015 | Expiration date: February 21, 2016 | Current use: Power plant | Permit id: 201502269393 | |||||
SCORE 100 New electric sign wall mount channel box led 3" thick white plastic face Date: December 23, 2014 Contractor: Steve Pham Permit type: Building permit | Permit id: #201412234402 | |||||
SCORE 95 2/f: replace deluge & heat detection system to accomodate new transformer. Contractor: Cosco Fire Protection Inc Permit type: Plumbing permit | Permit status: Complete | Permit id: Pp20150211947 | |||||
SCORE 95 Install lights outlets switches in dining area and kitchen. Install one exhaust fan on roof. One in bathroom lights 8 switches receptacles 2 fans and 1 dishwasher. Date: March 24, 2014 Contractor: J.W. Electrical And Const Permit type: Electrical permit | Permit status: Issued | Permit id: E201403248303 | |||||
SCORE 95 To obtain final inspection for electrical works that has been done to this site in 2007. Ref b200711158213 Date: September 18, 2012 Contractor: Cosco Fire Protection Inc Permit type: Electrical permit | Permit status: Issued | Permit id: E201209185199 | |||||
Street space permit and mta permit Permit type: Otc alterations permit | Permit status: Issued | Completion date: November 15, 2013 | Permit id: M444587 | |||||
SCORE 100 Construct partition wall between transformers 5 & 6 which will be 16 ft in height and 56 feet in length. Maher na Permit type: Building permit | Current use: Power plant | Permit id: #201601086709 | |||||
SCORE 93 1st floor: install replacement deluge system at transformer 6. Install new pilot sprinkler - release for tb 5 and 6. Relocate pipe stand for blast wall at tb 5 and 6 install pipe stands & nozzles per floor by tb - 5. Maher na Permit type: Building permit | Current use: Power plant | Permit id: #201602028547 | |||||
Performing a voluntary seismic strengthening of the electric substation including strengthening exterior connections shear connection constructing new shearwall & horizontal bracing & strengthening low roof diaphragm. See attached project description. Value: $500,000 Permit type: Additions alterations or repairs | Permit status: Complete | Completion date: March 13, 2007 | Expiration date: May 30, 2009 | Current use: Power plant | Permit id: 200703136168 | |||||
Existing restaurant t. I. /renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair/preserve original transom window. Date: December 11, 2013 Value: $185,200 Permit type: Building permit | Expiration date: December 11, 2014 | Current use: Food/beverage hndlng | Permit id: #201311222633 | |||||
Construct partition wall between transformers 5 & 6 which will be 16 ft in height and 56 feet in length. Maher na Date: February 5, 2016 Value: $60,001 Permit type: Building permit | Expiration date: February 5, 2017 | Current use: Power plant | Permit id: #201601086709 | |||||
SCORE 95 T. I. Deluge system re-work & new pipe. Date: February 12, 2016 Contractor: Cosco Fire Protection Inc Permit type: Plumbing permit | Permit status: Issued | Permit id: Pp20160212880 | |||||
Add new wet sprinkler system 15 heads in oil holding/over flow room & add new 39 nozzle water spram/deluge system on first floor transformer. Value: $51,564 Permit type: Additions alterations or repairs | Permit status: Issued | Completion date: November 19, 2007 | Expiration date: December 7, 2008 | Current use: Power plant | Permit id: 200711198527 | |||||
SCORE 93 Fire alarm system expansion and replace the graphic annunciator. Remove and replace the sprinkler manifold down the basement. Also install deluge system in bank 2 area to protect the new transformer. Permit type: Building permit | Expiration date: July 19, 2015 | Current use: Warehouse no frnitur | Permit id: #201307081325 | |||||
Street space and sidewalk Permit type: Otc alterations permit | Permit status: Filed | Completion date: July 18, 2002 | Permit id: M21199 | |||||
Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16. 5 ft high of pre-concrete. Maher n/a. Must maintain (e) fire suppression coverage. Date: July 23, 2014 Value: $50,000 Permit type: Building permit | Expiration date: July 25, 2015 | Current use: Power plant | Permit id: #201407231921 | |||||
SCORE 100 Install kitchen fire suppression system for hood and duct. Type: range guard ul 3 4 gallon. Permit type: Building permit | Expiration date: July 25, 2015 | Current use: Food/beverage hndlng | Permit id: #201407302509 | |||||
SCORE 100 To obtain final inspection for work approved under pa 200711158213; all work has been completed Permit type: Building permit | Expiration date: October 10, 2010 | Current use: Warehouse no frnitur | Permit id: #201006104246 | |||||
SCORE 100 Pg&e sub-station. To supply and install 6 heat detectors in transformer bank # 1 for activation of the existing deluge sprinkler system Permit type: Building permit | Expiration date: September 11, 2010 | Current use: Power plant | Permit id: #201003118001 | |||||
SCORE 95 Relocate four floor sink one toilet one sink one grease trap. Install three new floor drain. Install gas pipe for stove and water heater. Date: March 24, 2014 Contractor: J.W. Electrical And Const Permit type: Plumbing permit | Permit status: Issued | Permit id: Pp20140324289 | |||||
Replace (e) deluge & heat detection system to accommodate new transformer. Maher: compliance with ordinance no# 155-13 not required Value: $140,000 Permit type: Additions alterations or repairs | Permit status: Issued | Completion date: September 5, 2014 | Expiration date: December 1, 2017 | Current use: Power plant | Permit id: 201409055569 | |||||
Existing restaurant t. I. /renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Date: November 22, 2013 Value: $185,200 Permit type: Building permit | Current use: Food/beverage hndlng | Permit id: #201311222633 | |||||
SCORE 95 Renewal of expired permit #pp20130708226 Date: October 1, 2015 Contractor: Cosco Fire Protection Inc Permit type: Plumbing permit | Permit status: Complete | Permit id: Pp20151001436 | |||||
SCORE 100 To obtain final inspectionfor work approved under pa#200711158213 all work has been completed. Permit type: Building permit | Expiration date: January 18, 2013 | Current use: Warehouse no frnitur | Permit id: #201209189982 | |||||
Reinstall 6 heat detectors in transformer bay #4 for activation of the deluge sprinkler system on ground floor. Value: $13,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: December 17, 2008 | Expiration date: December 12, 2009 | Current use: Power plant | Permit id: 200812178673 | |||||
New electric sign wall mount channel box led 3" thick white plastic face Value: $900 Permit type: Sign-errect | Permit status: Filed | Completion date: December 23, 2014 | Current use: Food/beverage hndlng | Permit id: 201412234402 | |||||
Pg&e sub-station. To supply and install 6 heat detectors in transformer bank # 1 for activation of the existing deluge sprinkler system Value: $18,700 Permit type: Otc alterations permit | Permit status: Issued | Completion date: March 11, 2010 | Expiration date: March 6, 2011 | Current use: Power plant | Permit id: 201003118001 | |||||
Street space permit and mta permit Permit type: Otc alterations permit | Permit status: Filed | Completion date: August 19, 2014 | Permit id: M511948 | |||||
Street and sidewalk permit Permit type: Otc alterations permit | Permit status: Issued | Completion date: July 7, 2009 | Permit id: M171525 | |||||
Reinstall heat detectors in transformer bank #5 for activation of the deluge sprinkler system. The system shall include 6 heat detectors around transformer bank #5 Value: $9,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: June 10, 2008 | Expiration date: December 10, 2008 | Current use: Power plant | Permit id: 200806104011 | |||||
Street space permit Permit type: Otc alterations permit | Permit status: Issued | Completion date: June 25, 2007 | Permit id: M74704 | |||||
Street space & sidewalk repair. Permit type: Otc alterations permit | Permit status: Issued | Completion date: April 16, 2014 | Permit id: M480527 | |||||
Reroofing Value: $63,000 Permit type: Otc alterations permit | Permit status: Complete | Completion date: July 26, 2007 | Expiration date: July 26, 2008 | Current use: Power plant | Permit id: 200707267823 | |||||
1st floor: install replacement deluge system at transformer 6. Install new pilot sprinkler - release for tb 5 and 6. Relocate pipe stand for blast wall at tb 5 and 6 install pipe stands & nozzles per floor by tb - 5. Maher na Value: $158,851 Permit type: Otc alterations permit | Permit status: Issued | Completion date: February 2, 2016 | Expiration date: February 12, 2017 | Current use: Power plant | Permit id: 201602028547 | |||||
Kitchen remodeling Value: $10,000 Permit type: Additions alterations or repairs | Permit status: Expired | Completion date: June 21, 1988 | Expiration date: March 7, 1989 | Current use: Food/beverage hndlng | Permit id: 8808292 | |||||
Fire alarm system expansion and replace the graphic annunciator. Remove and replace the sprinkler manifold down the basement. Also install deluge system in bank 2 area to protect the new transformer. Value: $345,000 Permit type: Additions alterations or repairs | Permit status: Complete | Completion date: July 8, 2013 | Expiration date: July 3, 2016 | Current use: Warehouse | Permit id: 201307081325 | |||||
To obtain final inspectionfor work approved under pa#200711158213 all work has been completed. Value: $1 Permit type: Otc alterations permit | Permit status: Issued | Completion date: September 18, 2012 | Expiration date: September 13, 2013 | Current use: Warehouse | Permit id: 201209189982 | |||||
A new nfs2-30 panel with 1 remote graphic annunicator. The system will include smokes 6 beam detectors 1 pull station 6 dual monitor modules 6 monitor modules 6 pull station for existing deluxe system & 1 weatherproof hornstrobe. Value: $153,700 Permit type: Additions alterations or repairs | Permit status: Issued | Completion date: November 15, 2007 | Expiration date: March 11, 2009 | Current use: Warehouse | Permit id: 200711158213 | |||||
To obtain final inspection for work approved under pa 200711158213; all work has been completed Value: $1 Permit type: Otc alterations permit | Permit status: Issued | Completion date: June 10, 2010 | Expiration date: June 5, 2011 | Current use: Warehouse | Permit id: 201006104246 | |||||
As built: revision to pa # 2015 0226 9393 & 2014 0905 5569. Revise sequence of operation matrix only to remove output column aj "touchscreen graphic annunciator" there is no actual/physical work under this permit. N/a for maher Value: $1 Permit type: Otc alterations permit | Permit status: Complete | Completion date: March 2, 2015 | Expiration date: February 25, 2016 | Current use: Power plant | Permit id: 201503029684 | |||||
Bldg use: apts./coml. Value: $400 Permit type: Additions alterations or repairs | Permit status: Complete | Completion date: September 24, 1982 | Expiration date: February 5, 1983 | Permit id: 8207814 | |||||
Replace existing water spray system at transformer bank 4 with new water spray system (deluge) Value: $45,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: December 11, 2008 | Expiration date: December 6, 2009 | Current use: Power plant | Permit id: 200812118309 | |||||
Install kitchen fire suppression system for hood and duct. Type: range guard ul 3 4 gallon. Value: $3,000 Permit type: Otc alterations permit | Permit status: Complete | Completion date: July 30, 2014 | Expiration date: July 25, 2015 | Current use: Food/beverage hndlng | Permit id: 201407302509 | |||||
Reroofing Value: $140,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: October 7, 2005 | Expiration date: October 7, 2006 | Current use: Power plant | Permit id: 200510075132 | |||||
Replace (e) water spray system at transformer bank #1 with new water spray system for the new transformer (e) deluge system Value: $15,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: March 11, 2010 | Expiration date: April 29, 2011 | Current use: Power plant | Permit id: 201003118007 | |||||
Replace nozzles on (e) water spray system protecting transformer bank 5 reference pa# 2007-1119-8527 Value: $1 Permit type: Otc alterations permit | Permit status: Issued | Completion date: December 11, 2008 | Expiration date: December 6, 2009 | Current use: Power plant | Permit id: 200812118312 | |||||
Hood and duct fire system Value: $1,100 Permit type: Additions alterations or repairs | Permit status: Expired | Completion date: February 27, 1989 | Expiration date: July 30, 1989 | Current use: Food/beverage hndlng | Permit id: 8903101 | |||||
Street space Permit type: Otc alterations permit | Permit status: Issued | Completion date: January 28, 2014 | Permit id: M460167 | |||||
Construct partition wall between transformers 5 & 6 which will be 16 ft in height and 56 feet in length. Maher na Value: $60,000 Permit type: Otc alterations permit | Permit status: Issued | Completion date: January 8, 2016 | Expiration date: February 5, 2017 | Current use: Power plant | Permit id: 201601086709 | |||||
SCORE 95 Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair preserve original transom window. Permit type: Building permit | Expiration date: December 11, 2014 | Current use: Food/beverage hndlng | Permit id: #201311222633 | |||||
SCORE 95 Construct partition wall between transformers 5 & 6 which will be 16 ft in height and 56 feet in length. Maher na Permit type: Building permit | Expiration date: February 5, 2017 | Current use: Power plant | Permit id: #201601086709 | |||||
SCORE 95 Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16. 5 ft high of pre-concrete. Maher n a. Must maintain (e) fire suppression coverage. Permit type: Building permit | Expiration date: July 25, 2015 | Current use: Power plant | Permit id: #201407231921 | |||||
Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Date: November 22, 2013 Value: $185,200 Permit type: Building permit | Current use: Food/beverage hndlng | Permit id: #201311222633 | |||||
Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair preserve original transom window. Date: November 22, 2013 Value: $185,200 Permit type: Otc alterations permit | Permit status: Complete | Expiration date: November 22, 2013 | Current use: Food/beverage hndlng | Permit id: 201311222633 | |||||
As built: revision to pa # 2015 0226 9393 & 2014 0905 5569. Revise sequence of operation matrix only to remove output column aj "touchscreen graphic annunciator" there is no actual physical work under this permit. N a for maher Date: March 2, 2015 Value: $1 Permit type: Otc alterations permit | Permit status: Complete | Expiration date: March 2, 2015 | Current use: Power plant | Permit id: 201503029684 | |||||
Add new wet sprinkler system 15 heads in oil holding over flow room & add new 39 nozzle water spram deluge system on first floor transformer. Date: November 19, 2007 Value: $51,564 Permit type: Additions alterations or repairs | Permit status: Issued | Expiration date: November 19, 2007 | Current use: Power plant | Permit id: 200711198527 | |||||
As built replace (e) deluge and heat detection system to accomodate new transformer reference 201409055569; maher n a Date: February 26, 2015 Value: $1 Permit type: Otc alterations permit | Permit status: Issued | Expiration date: February 26, 2015 | Current use: Power plant | Permit id: 201502269393 | |||||
Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16. 5 ft high of pre-concrete. Maher n a. Must maintain (e) fire suppression coverage. Date: July 23, 2014 Value: $50,000 Permit type: Otc alterations permit | Permit status: Complete | Expiration date: July 23, 2014 | Current use: Power plant | Permit id: 201407231921 | |||||
Bldg use: apts. Coml. Date: September 24, 1982 Value: $400 Permit type: Additions alterations or repairs | Permit status: Complete | Expiration date: September 24, 1982 | Permit id: 8207814 | |||||
2 f: replace deluge & heat detection system to accomodate new transformer. Permit status: Complete | Permit id: E201502116292 | |||||
To obtain final inspection for electrical works that has been done to this site in 2007. Ref b200711158213 Permit status: Expired | Permit id: E201209185199 | |||||
Replace the exiting graphic annunciator with new touch screen graphic annunciator. Install new dual monitor modules and releasing control modules to monitor the new water flow and tamper switches. Install nine (9) duct smoke sensor to the existing fire alarm system to monitor the fan units in the basement. Install six (6) high heat sensors in the transformer 2 bay. Add one acps 6 power supply and 7 horn strobes to the fire alarm system Permit status: Issued | Permit id: Ew20130711041 | |||||
Install lights outlets switches in dining area and kitchen. Install one exhaust fan on roof. One in bathroom lights 8 switches receptacles 2 fans and 1 dishwasher. Permit status: Complete | Permit id: E201403248303 | |||||
Install 8 heat detections Permit status: Complete | Permit id: Ew20150213501 | |||||
Comply with correction notice. Permit status: Complete | Permit id: E200904018319 | |||||
Life safety for permit #ew20130711041 2 hour test Permit status: Complete | Permit id: Ew20150807781 | |||||
Life safety for permit #ew20130711041 Permit status: Complete | Permit id: Ew20130729801 | |||||
Date: July 7, 2009 Permit status: A | Expiration date: July 7, 2009 | Permit id: Pp20090707514 | |||||
Renewalofexpiredpermit#pp20130708226 Date: October 1, 2015 Permit status: Complete | Expiration date: October 1, 2015 | Permit id: Pp20151001436 | |||||
Basement&1 f:delugenozzlesystem f-500system. Date: July 8, 2013 Permit status: Expired | Expiration date: July 8, 2013 | Permit id: Pp20130708226 | |||||
Installnewwaterspraysystemintransformerbank#4 Date: December 11, 2008 Permit status: Complete | Expiration date: December 11, 2008 | Permit id: Pp20081211516 | |||||
2ndfloor:replacesewerpipeundertheceiling Date: January 8, 2009 Permit status: Complete | Expiration date: January 8, 2009 | Permit id: Pp20090108232 | |||||
Replacewaterspraysystem@pg&etransformerw newwaterspraysystem. Date: May 4, 2010 Permit status: Expired | Expiration date: May 4, 2010 | Permit id: Pp20100504784 | |||||
Relocatefourfloorsink onetoilet onesink onegreasetrap. Installthreenewfloordrain. Installgaspipeforstoveandwaterheater. Date: March 24, 2014 Permit status: Expired | Expiration date: March 24, 2014 | Permit id: Pp20140324289 | |||||
Provideanewbasementsprinklersystem(15heads)andanewtransformersystem(31nozzles) Date: December 7, 2007 Permit status: Complete | Expiration date: December 7, 2007 | Permit id: Pp20071207178 | |||||
2 f:replacedeluge&heatdetectionsystemtoaccomodatenewtransformer. Date: February 11, 2015 Permit status: Complete | Expiration date: February 11, 2015 | Permit id: Pp20150211947 | |||||
T. I. Delugesystem re-work&newpipe. Date: February 12, 2016 Permit status: Complete | Expiration date: February 12, 2016 | Permit id: Pp20160212880 | |||||
Life safety for permit #ew20130711041 2 hour test Permit status: Complete | Permit id: Ew20150807781 | |||||
Comply with correction notice. Permit status: Complete | Permit id: E200904018319 | |||||
Install 8 heat detections Permit status: Complete | Permit id: Ew20150213501 | |||||
Install lights outlets switches in dining area and kitchen. Install one exhaust fan on roof. One in bathroom lights 8 switches receptacles 2 fans and 1 dishwasher. Permit status: Complete | Permit id: E201403248303 | |||||
Replace the exiting graphic annunciator with new touch screen graphic annunciator. Install new dual monitor modules and releasing control modules to monitor the new water flow and tamper switches. Install nine (9) duct smoke sensor to the existing fire alarm system to monitor the fan units in the basement. Install six (6) high heat sensors in the transformer 2 bay. Add one acps 6 power supply and 7 horn strobes to the fire alarm system Permit status: Issued | Permit id: Ew20130711041 | |||||
2 f: replace deluge & heat detection system to accomodate new transformer. Permit status: Complete | Permit id: E201502116292 | |||||
To obtain final inspection for electrical works that has been done to this site in 2007. Ref b200711158213 Permit status: Expired | Permit id: E201209185199 | |||||
Life safety for permit #ew20130711041 Permit status: Complete | Permit id: Ew20130729801 | |||||
Performing a voluntary seismic strengthening of the electric substation including strengthening exterior connections, shear connection, constructing new shearwall & horizontal bracing & strengthening low roof diaphragm. See attached project description. Date: May 30, 2007 Value: $500,000 Permit type: Additions alterations or repairs | Completion date: March 11, 2008 | Expiration date: March 13, 2007 | Current use: Power plant | Permit id: 200703136168 | |||||
Design and expand (e) fire alarm system to cover the new building addition, ref pa 201511233360, add 1 power supply, 9 notification, 19 initiating. Note: lots have been merged, to block 0335 lot 037. N a ordinance #155-13 Date: February 6, 2017 Value: $28,000 Permit type: Otc alterations permit | Expiration date: February 6, 2017 | Current use: Power plant | Permit id: 201702068696 | |||||
A new nfs2-30 panel with 1 remote graphic annunicator. The system will include smokes, 6 beam detectors, 1 pull station, 6 dual monitor modules, 6 monitor modules, 6 pull station for existing deluxe system & 1 weatherproof hornstrobe. Date: March 11, 2008 Value: $153,700 Permit type: Additions alterations or repairs | Expiration date: November 15, 2007 | Current use: Warehouse,no frnitur | Permit id: 200711158213 | |||||
Remove extg 4"x3"(2-way)fire depart connection and relocate on same side of bldg to west. Ref app#201601086709. N a for maher. Date: December 28, 2017 Value: $4,300 Permit type: Otc alterations permit | Expiration date: December 28, 2017 | Current use: Power plant | Permit id: 201712287573 | |||||
Replace nozzles on (e) water spray system protecting transformer bank 5, reference pa# 2007-1119-8527 Date: December 11, 2008 Value: $1 Permit type: Otc alterations permit | Expiration date: December 11, 2008 | Current use: Power plant | Permit id: 200812118312 | |||||
Replace (e) water spray system at transformer bank #1 with new water spray system for the new transformer, (e) deluge system Date: May 4, 2010 Value: $15,000 Permit type: Otc alterations permit | Expiration date: March 11, 2010 | Current use: Power plant | Permit id: 201003118007 | |||||
Existing restaurant t. I. Renovation including renovated comm kitchen, food prep area, seating area, interior lighting, plumbing & electrical work, new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair preserve original transom window. Date: December 11, 2013 Value: $185,200 Permit type: Otc alterations permit | Completion date: March 18, 2015 | Expiration date: November 22, 2013 | Current use: Food/beverage hndlng | Permit id: 201311222633 | |||||
New electric sign, wall mount channel box led 3" thick white plastic face Date: December 23, 2014 Value: $900 Permit type: Sign - erect | Expiration date: December 23, 2014 | Current use: Food/beverage hndlng | Permit id: 201412234402 | |||||
As built replace (e) deluge and heat detection system to accomodate new transformer, reference 201409055569; maher n a Date: February 26, 2015 Value: $1 Permit type: Otc alterations permit | Expiration date: February 26, 2015 | Current use: Power plant | Permit id: 201502269393 | |||||
1st floor: install replacement deluge system at transformer 6. Install new pilot sprinkler - release for tb 5 and 6. Relocate pipe stand for blast wall at tb 5 and 6, install pipe stands & nozzles per floor by tb - 5. Maher na Date: February 12, 2016 Value: $158,851 Permit type: Otc alterations permit | Expiration date: February 2, 2016 | Current use: Power plant | Permit id: 201602028547 | |||||
1 exterior sign. 1 led white lighting, 1 class 2 power supply 12v, 1 light, 1 switch. Date: February 19, 2015 Permit status: Complete | Completion date: March 11, 2015 | Permit id: E201502196467 | |||||
Life safety for permit #ew20130711041 2 hour test Date: August 7, 2015 Permit status: Complete | Completion date: September 8, 2015 | Permit id: Ew20150807781 | |||||
Install lights, outlets, switches in dining area and kitchen. Install one exhaust fan on roof. One in bathroom lights, 8 switches, receptacles, 2 fans and 1 dishwasher. Date: March 24, 2014 Permit status: Complete | Completion date: March 11, 2015 | Permit id: E201403248303 | |||||
To obtain final inspection for electrical works that has been done to this site in 2007. Ref b200711158213 Date: September 18, 2012 Permit status: Expired | Permit id: E201209185199 | |||||
Life safety for permit #ew20130711041 Date: July 29, 2013 Permit status: Complete | Completion date: July 31, 2013 | Permit id: Ew20130729801 | |||||
Design and expand the existing fire alarm control panel to cover the new addition. Date: February 6, 2017 Permit status: Issued | Permit id: E201702062734 | |||||
Replace the exiting graphic annunciator with new touch screen graphic annunciator. Install new dual monitor modules and releasing control modules to monitor the new water flow and tamper switches. Install nine (9) duct smoke sensor to the existing fire alarm system to monitor the fan units in the basement. Install six (6) high heat sensors in the transformer 2 bay. Add one acps 6 power supply and 7 horn strobes to the fire alarm system Date: July 11, 2013 Permit status: Issued | Permit id: Ew20130711041 | |||||
Install 8 heat detections Date: February 13, 2015 Permit status: Complete | Completion date: February 17, 2015 | Permit id: Ew20150213501 | |||||
2 f: replace deluge & heat detection system to accomodate new transformer. Date: February 11, 2015 Permit status: Complete | Completion date: March 4, 2015 | Permit id: E201502116292 | |||||
Comply with correction notice. Date: April 1, 2009 Permit status: Complete | Completion date: June 1, 2009 | Permit id: E200904018319 | |||||
Install new water spray system in transformer bank #4 Date: December 11, 2008 Permit status: Complete | Completion date: December 22, 2008 | Expiration date: December 11, 2008 | Permit id: Pp20081211516 | |||||
Renewal of expired permit #pp20130708226 Date: October 1, 2015 Permit status: Complete | Completion date: October 2, 2015 | Expiration date: October 1, 2015 | Permit id: Pp20151001436 | |||||
T. I. Deluge system, re-work & new pipe. Date: February 12, 2016 Permit status: Complete | Completion date: June 27, 2016 | Expiration date: February 12, 2016 | Permit id: Pp20160212880 | |||||
Provide a new basement sprinkler system (15 heads) and a new transformer system (31 nozzles) Date: December 7, 2007 Permit status: Complete | Completion date: July 31, 2008 | Expiration date: December 7, 2007 | Permit id: Pp20071207178 | |||||
2nd floor: replace sewer pipe under the ceiling Date: January 8, 2009 Permit status: Complete | Completion date: February 5, 2009 | Expiration date: January 8, 2009 | Permit id: Pp20090108232 | |||||
Repair sewer - underground Date: July 7, 2009 Permit status: Expired | Expiration date: July 7, 2009 | Permit id: Pp20090707514 | |||||
Relocate four floor sink, one toilet, one sink, one grease trap. Install three new floor drain. Install gas pipe for stove and water heater. Date: March 24, 2014 Permit status: Expired | Expiration date: March 24, 2014 | Permit id: Pp20140324289 | |||||
Basement & 1 f: deluge nozzle system, f-5 system. Date: July 8, 2013 Permit status: Expired | Expiration date: July 8, 2013 | Permit id: Pp20130708226 | |||||
Replace water spray system @ p g & e transformer w new water spray system. Date: May 4, 2010 Permit status: Expired | Expiration date: May 4, 2010 | Permit id: Pp20100504784 | |||||
Relocate (e) fdc to same side of bldg to west Date: December 28, 2017 Permit status: Issued | Expiration date: December 28, 2017 | Permit id: Pp20171228534 | |||||
SCORE 95 Existing restaurant t. I. Renovation including renovated comm kitchen food prep area seating area interior lighting plumbing & electrical work new accessible bathroom & partial storefront. Mech under separate permit. Expose & repair preserve original transom window. Permit type: Building permit | Expiration date: December 11, 2014 | Current use: Food/beverage hndlng | Permit id: #201311222633 | |||||
SCORE 93 Remove extg 4"x3"(2-way)fire depart connection and relocate on same side of bldg to west. Ref app#201601086709. N a for maher. Permit type: Building permit | Expiration date: April 28, 2018 | Current use: Power plant | Permit id: #201712287573 | |||||
SCORE 95 Relocate (e) fdc to same side of bldg to west Date: December 28, 2017 Contractor: Cosco Fire Protection Inc Permit type: Plumbing permit | Permit status: Issued | Permit id: Pp20171228534 | |||||
SCORE 95 2/f: replace deluge & heat detection system to accomodate new transformer. Date: March 4, 2015 Contractor: Cosco Fire Protection Inc Permit type: Electrical permit | Permit status: Complete | Permit id: E201502116292 | |||||
SCORE 93 As built replace (e) deluge and heat detection system to accomodate new transformer reference 201409055569; maher n/a Permit type: Building permit | Expiration date: February 21, 2016 | Current use: Power plant | Permit id: #201502269393 | |||||
SCORE 95 Design and expand the existing fire alarm control panel to cover the new addition. Date: February 6, 2017 Contractor: Cosco Fire Protection Inc Permit type: Electrical permit | Permit status: Issued | Permit id: E201702062734 | |||||
SCORE 93 Design and expand (e) fire alarm system to cover the new building addition ref pa 2015112333 add 1 power supply 9 notification 19 initiating. Note: lots have been merged to block 0335 lot 037. N a ordinance #155-13 Permit type: Building permit | Expiration date: February 6, 2018 | Current use: Power plant | Permit id: #201702068696 | |||||
SCORE 95 Basement & 1/f: deluge nozzle system f-5 system. Date: July 8, 2013 Contractor: Cosco Fire Protection Inc Permit type: Plumbing permit | Permit status: Issued | Permit id: Pp20130708226 | |||||
SCORE 95 Construct partition walls between transformers 3 and 4 on 1st floor - 24 ft and 16. 5 ft high of pre-concrete. Maher n a. Must maintain (e) fire suppression coverage. Permit type: Building permit | Expiration date: July 25, 2015 | Current use: Power plant | Permit id: #201407231921 | |||||
SCORE 100 Replace (e) water spray system at transformer bank #1 with new water spray system for the new transformer (e) deluge system Permit type: Building permit | Expiration date: November 4, 2010 | Current use: Power plant | Permit id: #201003118007 | |||||
SCORE 93 As built: revision to pa # 2015 0226 9393 & 2014 0905 5569. Revise sequence of operation matrix only to remove output column aj "touchscreen graphic annunciator" there is no actual/physical work under this permit. N/a for maher Permit type: Building permit | Expiration date: February 25, 2016 | Current use: Power plant | Permit id: #201503029684 | |||||
SCORE 93 Replace (e) deluge & heat detection system to accommodate new transformer. Maher: compliance with ordinance no# 155-13 not required Permit type: Building permit | Current use: Power plant | Permit id: #201409055569 |