SCORE 86 2393 Woodward St Philadelphia Pa 191155102 Installation of new diesel fire pump in accordance with nfpa in an existing accessory out-building, formerly used as a salt shed. Pump to be used to provide an automatic water supply to the existing dry standpipe systems in two residential high-rise structures on separately deeded lots, but under common ownership - evergreen tower @ 2393 woodward st. And plaza tower @ 24 tremont st., permit also includes installation of underground fire service in accordance with nfpa 13 from the tap in woodward st to the fire pump, and from the pump to the standpipe connection in the basement levels of both buildings, as well as all modifications to the existing manual dry systems required for the conversion to automatic wet in accordance with nfpa 14. All six existing standpipes (3 in ech building) will be extended to new roof hydrants and will be used to supply automatic sprinkler in both buildings. Separate building and zoning permits required for the conversion of the existing salt shed for use as Date: June 5, 2015 Contractor: Guy M Cooper Inc Client: Evergreen Park Manor Corp | Client Company: Revere Real Estate | Permit type: Suppression permit | Permit status: Completed | Completion date: April 12, 2016 | Permit id: 578407 | |||||
SCORE 86 24 Tremont St Philadelphia Pa 191155007 Aministrative permit to document conversion of dry standpipe to wet. All modifications to the existing dry system, including installtaion of underground service from a shared fire pump, completed under permit #578407 for 2393 woodward st. Date: June 5, 2015 Contractor: Guy M Cooper Inc Client: Evergreen Park Manor | Client Company: Revere Suburban Real Est | Permit type: Administrative permit | Permit status: Completed | Completion date: April 12, 2016 | Permit id: 609194 | |||||
SCORE 86 24 Tremont St Philadelphia Pa 191155007 Relocate 6 sprinkler heads (plaza tower basement) - see hansen case #347302 Date: January 17, 2013 Contractor: Guy M Cooper Inc Client: Evergreen Park Manor | Client Company: Revere Suburban Real Est | Permit type: Suppression permit | Permit status: Expired | Completion date: October 29, 2014 | Permit id: 448713 | |||||
SCORE 86 Date: April 29, 2013 Contractor: Guy M Cooper Inc Permit type: Suppression permit | Permit status: Completed | Completion date: February 27, 2014 | Permit id: 468023 | |||||
SCORE 86 Date: April 29, 2013 Contractor: Guy M Cooper Inc Permit type: Suppression permit | Permit status: Completed | Completion date: December 30, 2013 | Permit id: 468025 | |||||
SCORE 86 1234 Market St Philadelphia Pa 191073615 Install a nfpa standard double interlock pre action sprinkler system to project room 103a. System energized by connection to existing wet pipe sprinkler main in adjacent space. Date: March 20, 2014 Contractor: Guy M Cooper Inc Client: Septa | Client Company: Us Equities Mgt Llc | Permit type: Suppression permit | Permit status: Expired | Completion date: May 27, 2015 | Permit id: 519296 | |||||
SCORE 86 1234 Market St Philadelphia Pa 191073615 Remove existing wet pipe sprinklers in renovated space, install new double interlock preaction sprinkler system fed from existing adjacent wet pipe sprinkler zone on 20th floor, which is tied into the building standpipe. Date: January 6, 2014 Contractor: Guy M Cooper Inc Client: Septa | Client Company: Us Equities Mgt Llc | Permit type: Suppression permit | Permit status: Expired | Completion date: June 9, 2015 | Permit id: 507292 | |||||
SCORE 86 Date: December 22, 2015 Contractor: Guy M Cooper Inc Client: Young Michael F Tr | Permit type: Plumbing permit | Permit status: Completed | Completion date: January 23, 2016 | Permit id: 659286 | |||||
SCORE 86 2393 Woodward St Philadelphia Pa 191155102 Installation of new floor drain in new fire pump room. Tie into existing building sanitary line Date: February 11, 2015 Contractor: Guy M Cooper Inc Client: Evergreen Park Manor Corp | Client Company: Revere Real Estate | Permit type: Plumbing permit | Permit status: Completed | Completion date: April 12, 2016 | Permit id: 586618 | |||||
SCORE 86 9503 State Rd Philadelphia Pa 191143098 Interior plumbing alterations to an existing (6)story apartment building to creat 135 dwelling units per the approved plans p000, p001, p002, p003, p004, p101, p102, p103, p104, p200, p201, p3 and the philadelphia plumbing code 2004 (fourth printing) Date: November 19, 2013 Contractor: Guy M Cooper Inc Client: Bakers Bay Elderly Associ | Permit type: Plumbing permit | Permit status: Completed | Completion date: May 4, 2015 | Permit id: 499533 | |||||
SCORE 86 9503 State Rd Philadelphia Pa 191143098 Installation of a complete underground storm water infiltration system and (3)catch basins - tie into the existing 24" storm line with a new 15" lateral connection - note: all work on "private" property - "all excavations and plumbing trenches in excess of 5 feet in depth must have approved shoring in place at the time of inspection" Date: June 3, 2014 Contractor: Guy M Cooper Inc Client: Bakers Bay Elderly Associ | Permit type: Plumbing permit | Permit status: Completed | Completion date: September 3, 2014 | Permit id: 533881 | |||||
SCORE 86 1234 Market St Philadelphia Pa 191073615 Install cold water supply and back flow preventor to hvac units install make up cold water supply to 4 hvac units protect the make up water supply piping with (2) 3 4" backflow prevention isolation devices (office space) Date: November 19, 2013 Contractor: Guy M Cooper Inc Client: Septa | Client Company: Us Equities Mgt Llc | Permit type: Plumbing permit | Permit status: Expired | Completion date: June 9, 2015 | Permit id: 506885 | |||||
SCORE 86 1234 Market St Philadelphia Pa 191073615 Install cold water supply and backflow preventor to hvac units (office space) Date: April 9, 2014 Contractor: Guy M Cooper Inc Client: Septa | Client Company: Us Equities Mgt Llc | Permit type: Plumbing permit | Permit status: Completed | Completion date: January 14, 2015 | Permit id: 519322 |