SCORE 86 Client: Card Readers | Permit type: Com: addition | Permit status: Expired | Current use: Commercial | Permit id: 05-01295 | Parcel: 11153 | |||||
SCORE 86 Client: Card Access G279 | Permit type: Com: remodel | Permit status: Expired | Current use: Commercial | Permit id: 06-01083 | Parcel: 12503 | |||||
SCORE 86 Client: Mission-Card Readers | Permit type: Com: remodel | Permit status: Expired | Current use: Commercial | Permit id: 05-02618 | Parcel: 20919 | |||||
SCORE 86 Client: Card Reader A15617 | Permit type: Com: remodel | Permit status: Expired | Current use: Commercial | Permit id: 05-03439 | Parcel: 11153 | |||||
SCORE 86 Client: Mssion 2nd Floor Card Acc | Permit type: Com: remodel | Permit status: Expired | Current use: Commercial | Permit id: 05-04673 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: tue aug 24 00:00: edt 2004 - commercial installation of card reader mission campus 2 doors 5th floor nursing station ;scc; comment date: thu aug 26 00:00: edt 2004 - fire prevention plan Client: Msj 5th Floor Nursing | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-04048 | Parcel: 23186 | |||||
SCORE 86 428 Biltmore Ave, Asheville, Nc 28801 Comment date: mon aug 23 00:00: edt 2004 - commercial installation of card reader st. Joseph campus rear door second floor pharmacy;scc; comment date: wed sep 01 00:00: edt 2004 - for building inspe Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-04034 | Parcel: 11153 | |||||
SCORE 86 428 Biltmore Ave, Asheville, Nc 28801 Comment date: fri oct 01 00:00: edt 2004 - st joseph hospital - install 1 access control card reader on 1st floor. Pmd; comment date: thu nov 04 00:00: est 2004 - fire prevention plan review comments: Client: Misson Control Reader | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-05007 | Parcel: 11153 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: mon aug 23 00:00: edt 2004 - commercial installation of card reader first door second floor or;scc; comment date: wed sep 01 00:00: edt 2004 - for building inspections call harry taylo Client: Ist Door Msj 2nd Floor Or | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-04033 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: fri oct 01 00:00: edt 2004 - mission hospital - install 5 access control card readers on exterior doors. Pmd; comment date: thu nov 04 00:00: est 2004 - fire prevention plan review comme Client: Misson Control Reader | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-05005 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: mon nov 08 00:00: est 2004 - install 1 card access reader on mission campus door 104 sfb; comment date: thu nov 18 00:00: est 2004 - fire prevention plan review comments: mmh door x104 c Client: Mission Hospital | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-05760 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: wed nov 17 00:00: est 2004 - install card reader on doors b318 and b324 sfb; comment date: mon nov 29 00:00: est 2004 - for building inspections call harry taylor at redacted phone num Client: Mission Hospital | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-05970 | Parcel: 23186 | |||||
SCORE 86 428 Biltmore Ave, Asheville, Nc 28801 Comment date: wed sep 08 00:00: edt 2004 - installing one access control card reader at 1st floor entrance to badging area. Lcs; comment date: fri sep 00:00: edt 2004 - fire prevention review comments Permit type: Com: electrical | Permit status: Closed | Current use: Commercial | Permit id: 04-04293 | Parcel: 11153 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: tue nov 02 00:00: est 2004 - mission hospital - install 1 access control card readers on door b326. Pmd; comment date: mon nov 08 00:00: est 2004 - fire prevention plan review comments: Client: Misson Control Reader | Permit type: Com: other new | Permit status: Expired | Current use: Commercial | Permit id: 04-05669 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Comment date: fri mar 12 00:00: est 2004 - mission-adding card readers on three doors on mission hospital pediatrics on 3rd floor. Includes in/out card readers, boxs, emergency buttons, sounder, and c Client: Card Readers-Best Access | Permit type: Com: remodel | Permit status: Expired | Current use: Commercial | Permit id: 04-01120 | Parcel: 23186 | |||||
SCORE 86 509 Biltmore Ave, Asheville, Nc 28801 Card access door packageon both interior entrances and stairwell;scc; holding for further internal information on locking devices on exit door; fire prevention plan review comments: 3rd floor, mmh heart tower call for fire inspections at redacted phone number, jeff payne or lewis garrison. Read comments sheet 1. Stair door cannot lock on the egress side. 2 . 2 locking methods are not allowed in the total path of eg ress 3. Installation to meet ifc and ibc section 1003. 3. 1. 8. 5 (at tached) 4. N eed unlocking devices at nurses station (3. D.) 5. Ca ll fire inspector at electric rough in to confirm locat ion of exit signs and emergency lighting 6. Special locking arrangement shall connect to the fire a larm to disconnect to all egress. 7 . Fire alarm plans. A permit amendment, plans, and sp ecifications for fire alarm systems shall be submitted an d approved prior to system installation. Will test alarm ti e to building fire alarm at final fire inspection. Fire al arm installer must obtain a fire Client: Mssion Card Acc | Permit type: Com: remodel | Permit status: Closed | Current use: Commercial | Permit id: 06-00473 | Parcel: 23186 | |||||
SCORE 86 428 Biltmore Ave, Asheville, Nc 28801 Card readers on b202 nd video a phone. Clc; building safety review comments the approved plans with the attached review comments are required to be at the job site for use by the field inspector(s) at all times. The building permit is required to be posted at the jobsite at all times. Failure to post approved permits & plans at site is a fine, fine must be paid before next inspection is requested. For building inspections call harry taylor at redacted phone number. All subcontractors need to complete trade application for project. Subcontractors need to either visit the permit office or fax copy of application to (828)redacted phone number for activation of electrical, plumbing or mechanical permits.; fire prevention plan review comments: st joe campus b202 and data room call for fire inspections at redacted phone number, jeff payne or lewis garrison. Read comments sheet 1. Call fire inspector at electric rough in to confirm l ocation of exit signs and emergency light Client: Mission Hospital | Permit type: Com: upfit | Permit status: Closed | Current use: Commercial | Permit id: 05-04318 | Parcel: 11153 |